Siemens

Overview

SITOP PSU6200 family 24 V

High performance – Focused diagnostics – The all-round power supply for a wide variety of applications

The SITOP PSU6200 product family is the new standard power supply for customers with extreme technical requirements regarding reliability, efficiency and integration. It is suitable for many fields of application, particularly in the industrial environment, such as series machine building. The SITOP PSU6200 represents the state-of-the-art and takes the prized SITOP design to new dimensions of efficiency.

The stabilized 1-phase power supplies with a wide input range of 120–230 V AC nominal voltage and 120–240 V DC are available with an output voltage of 12 V in three performance classes and with an output voltage of 24 V in six performance classes.

The premium design of the PSU6200 series, in connection with the push-in terminals, represents effective wiring. The modules in this product family are all-rounders featuring a long service life and absolute reliability.

The high level of efficiency across the entire load range, as well as the minimal no-load losses, result in lower overall energy consumption. New levels of convenience during commissioning and service are offered for modules of 10 A or more by the diagnostic monitor with LED indicators for DC o.k., utilization and service life, as well as the diagnostics interface for reporting status information. For power supplies with an output of more than 10 A, the DC o.k. status is also equipped with glitch recognition that indicates even the smallest supply voltage failures.

For power supply modules up to 10 A, a diagnostics LED indicates DC o.k.; this information is also reported by means of a relay for devices of 3.7 A and above.

Main product highlights
  • Diagnostic monitor from 10 A output performance
    • LED display for DC o.k., utilization and operating hours
  • Diagnostics interface from 10 A output performance
    • Provision of important operating parameters (e.g. power, voltage, overload, etc.)
  • Constant current
    • Up to 15 V supply voltage for 24 V devices, up to 9 V supply voltage for 12 V devices
    • Power supply not switched off immediately in the event of overload
  • Robust AC input
    • Active PFC
    • Optimized protection of the input circuit
  • DC capability / wide-range input
    • Enhanced versatility and reliability
  • Coordinated product family
    • Comprehensive range of products for a wide range of requirements
  • Narrow overall width
    • For direct side-by-side mounting without lateral clearance requirements
    • Attractive metal enclosures from 3.7 A, plastic enclosure up to 2.5 A with similar form and color
  • Push-in terminals
    • Easy, time-saving installation without need for tools
    • Separate ground terminal
  • Selectivity and redundancy modules
    • Narrow width
    • In SITOP PSU6200 design

Technical specifications

Article number

6EP3331-7SB00-0AX0

6EP3332-7SB00-0AX0

6EP3333-7LB00-0AX0

Product

SITOP PSU6200

SITOP PSU6200

SITOP PSU6200

Power supply, type

24 V/1.3 A

24 V/2.5 A

24 V/3.7 A

Input

Input

1-phase AC or DC

1-phase AC or DC

1-phase AC or DC

Rated voltage value Vin rated

120 … 230 V

120 … 230 V

120 … 230 V

Voltage range AC

85 … 264 V

85 … 264 V

85 … 264 V

Supply voltage

  • ● at DC

120 … 240 V

120 … 240 V

120 … 240 V

Input voltage

  • ● at DC

110 … 275 V

110 … 275 V

99 … 275 V

Wide-range input

Yes

Yes

Yes

Overvoltage resistance

300 V AC for 30 s

300 V AC for 30 s

300 V AC for 30 s

Mains buffering at Iout rated, min.

150 ms; at Vin = 230 V

150 ms; at Vin = 230 V

90 ms; at Vin = 230 V

Rated line frequency 1

50 Hz

50 Hz

50 Hz

Rated line frequency 2

60 Hz

60 Hz

60 Hz

Rated line range

47 … 63 Hz

47 … 63 Hz

47 … 63 Hz

Input current

  • ● at rated input voltage 120 V

0.6 A

1.1 A

1.5 A

  • ● at rated input voltage 230 V

0.3 A

0.6 A

0.9 A

Switch-on current limiting (+25 °C), max.

32 A

32 A

29 A

Built-in incoming fuse

3.15 A

3.15 A

3.15 A

Output

Output

Controlled, isolated DC voltage

Controlled, isolated DC voltage

Controlled, isolated DC voltage

Number of outputs

1

1

1

Rated voltage Vout DC

24 V

24 V

24 V

Total tolerance, static ±

3 %

3 %

3 %

Static mains compensation, approx.

0.1 %

0.1 %

0.2 %

Static load balancing, approx.

0.1 %

0.1 %

0.3 %

Residual ripple peak-peak, max.

30 mV

30 mV

30 mV

Residual ripple peak-peak, typ.

20 mV

20 mV

20 mV

Spikes peak-peak, max. (bandwidth: 20 MHz)

30 mV

30 mV

100 mV

Spikes peak-peak, typ. (bandwidth: 20 MHz)

20 mV

20 mV

60 mV

Adjustment range

22.2 … 26.4 V

22.2 … 26.4 V

24 … 28 V

Product function Output voltage adjustable

Yes

Yes

Yes

Output voltage setting

via potentiometer; max. 31.2 W

via potentiometer; max. 60 W

via potentiometer; max. 89 W (106 W up to 45°C)

Status display

Green LED for 24 V OK

Green LED for 24 V OK

Green LED for 24 V OK

Signaling

Electronic contact (NO contact, contact rating 60 V DC/0.1 A) for 24 V O.K. or diagnostic interface

On/off behavior

Overshoot of Vout approx. 3 %

Overshoot of Vout approx. 3 %

Overshoot of Vout < 2 %

Startup delay, max.

1 s

1 s

0.5 s

Voltage rise, typ.

50 ms

100 ms

100 ms

Rated current value Iout rated

1.3 A

2.5 A

3.7 A

Current range

0 … 1.3 A

0 … 2.5 A

0 … 3.7 A

  • ● Note

+60 … +70 °C: Derating 2.5%/K

+60 … +70 °C: Derating 1.5%/K

Supplied active power typical

31.2 W

60 W

89 W

Short-term overload current

  • ● on short-circuiting during the start-up typical

1.3 A

2.5 A

3.7 A

  • ● at short-circuit during operation typical

1.3 A

2.5 A

3.7 A

Efficiency

Efficiency at Vout rated, Iout rated, approx.

86.3 %

89 %

89.3 %

Power loss at Vout rated, Iout rated, approx.

5 W

7 W

11 W

Power loss [W] during no-load operation maximum

0.8 W

0.8 W

2.2 W

Closed-loop control

Dynamic load smoothing (Iout: 10/90/10 %), Uout ± typ.

2 %

3 %

2 %

Load step setting time 10 to 90%, typ.

0.5 ms

1 ms

2 ms

Load step setting time 90 to 10%, typ.

0.5 ms

1 ms

2 ms

Setting time maximum

1 ms

2 ms

3 ms

Protection and monitoring

Output overvoltage protection

< 32 V

< 32 V

< 32 V

Current limitation, typ.

1.6 A

3.1 A

3.7 A

Property of the output Short-circuit proof

Yes

Yes

Yes

Short-circuit protection

Shutdown and periodic restart attempts

Shutdown and periodic restart attempts

Shutdown and periodic restart attempts

Safety

Primary/secondary isolation

Yes

Yes

Yes

Galvanic isolation

Safety extra low output voltage Vout according to EN 60950-1

Safety extra low output voltage Vout according to EN 60950-1

Safety extra low output voltage Vout according to EN 60950-1

Protection class

Class I

Class I

Class I

Leakage current

  • ● maximum

3.5 mA

3.5 mA

3.5 mA

CE mark

Yes

Yes

Yes

UL/cUL (CSA) approval

cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)

cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)

cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)

Explosion protection

FM approval

CB approval

Yes

Yes

Yes

Regulatory Compliance Mark (RCM)

No

No

No

Marine approval

in process: DNV GL, ABS

in process: DNV GL, ABS

in process: DNV GL, ABS

Degree of protection (EN 60529)

IP20

IP20

IP20

EMC

Emitted interference

EN 55022 Class B

EN 55022 Class B

EN 55022 Class B

Supply harmonics limitation

EN 61000-3-2

EN 61000-3-2

EN 61000-3-2

Noise immunity

EN 61000-6-2

EN 61000-6-2

EN 61000-6-2

Operating data

Ambient temperature

  • ● during operation

-25 … +70 °C

-25 … +70 °C

-25 … +70 °C

  • — Note

with natural convection

with natural convection

with natural convection

  • ● during transport

-40 … +85 °C

-40 … +85 °C

-40 … +85 °C

  • ● during storage

-40 … +85 °C

-40 … +85 °C

-40 … +85 °C

Humidity class according to EN 60721

Climate class 3K3, 5 … 95% no condensation

Climate class 3K3, 5 … 95% no condensation

Climate class 3K3, 5 … 95% no condensation

Mechanics

Connection technology

Push-in terminals

Push-in terminals

Push-in terminals

Connections

  • ● Supply input

L1/+, L2/N/-; PE PushIn for 0.5 … 2.5 mm² single-core/finely stranded

L1/+, L2/N/-; PE PushIn for 0.5 … 2.5 mm² single-core/finely stranded

L1/+, L2/N/-; PE PushIn for 0.5 … 4 mm² single-core/finely stranded

  • ● Output

+1, -1, -2: PushIn for 0.5 … 2.5 mm²

+1, -1, -2: PushIn for 0.5 … 2.5 mm²

+1, +2, -1, -2, -3: PushIn for 0.5 … 2.5 mm²

  • ● Auxiliary

13, 14 (alarm signal): 1 push-in terminal each for 0.2 … 1.5 mm²

Width of the enclosure

25 mm

40 mm

35 mm

Height of the enclosure

100 mm

100 mm

135 mm

Depth of the enclosure

88 mm

88 mm

125 mm

Required spacing

  • ● top

50 mm

50 mm

45 mm

  • ● bottom

50 mm

50 mm

45 mm

  • ● left

0 mm

0 mm

0 mm

  • ● right

0 mm

0 mm

0 mm

Product feature of the enclosure housing for side-by-side mounting

Yes

Yes

Yes

Installation

Snaps onto DIN rail EN 60715 35×7.5/15

Snaps onto DIN rail EN 60715 35×7.5/15

Snaps onto DIN rail EN 60715 35×7.5/15

Electrical accessories

Buffer module, redundancy module

Buffer module, redundancy module

Buffer module, redundancy module

Mechanical accessories

Identification labels SIMATIC ET 200SP 6ES7193-6LF30-0AW0

Identification labels SIMATIC ET 200SP 6ES7193-6LF30-0AW0

Identification labels SIMATIC ET 200SP 6ES7193-6LF30-0AW0

Other information

Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

Article number

6EP3333-7SB00-0AX0

6EP3334-7SB00-3AX0

6EP3336-7SB00-3AX0

Product

SITOP PSU6200

SITOP PSU6200

SITOP PSU6200

Power supply, type

24 V/5 A

24 V/10 A

24 V/20 A

Input

Input

1-phase AC or DC

1-phase AC or DC

1-phase AC or DC

Rated voltage value Vin rated

120 … 230 V

120 … 230 V

120 … 230 V

Voltage range AC

85 … 264 V

85 … 264 V

85 … 264 V

Supply voltage

  • ● at DC

120 … 240 V

110 … 240 V

110 … 240 V

Input voltage

  • ● at DC

99 … 275 V

85 … 275 V

85 … 275 V

Wide-range input

Yes

Yes

Yes

Overvoltage resistance

300 V AC for 30 s

300 V AC for 30 s

300 V AC for 30 s

Mains buffering at Iout rated, min.

80 ms; at Vin = 230 V

45 ms; at Vin = 230 V

25 ms; at Vin = 230 V

Rated line frequency 1

50 Hz

50 Hz

50 Hz

Rated line frequency 2

60 Hz

60 Hz

60 Hz

Rated line range

47 … 63 Hz

47 … 63 Hz

47 … 63 Hz

Input current

  • ● at rated input voltage 120 V

1.9 A

2.2 A

4.3 A

  • ● at rated input voltage 230 V

1.1 A

1.2 A

2.3 A

Switch-on current limiting (+25 °C), max.

29 A

6 A

12 A

Built-in incoming fuse

3.15 A

5 A

10 A

Output

Output

Controlled, isolated DC voltage

Controlled, isolated DC voltage

Controlled, isolated DC voltage

Number of outputs

1

1

1

Rated voltage Vout DC

24 V

24 V

24 V

Total tolerance, static ±

3 %

3 %

3 %

Static mains compensation, approx.

0.1 %

0.1 %

0.2 %

Static load balancing, approx.

0.2 %

0.1 %

0.2 %

Residual ripple peak-peak, max.

30 mV

30 mV

80 mV

Residual ripple peak-peak, typ.

20 mV

20 mV

50 mV

Spikes peak-peak, max. (bandwidth: 20 MHz)

100 mV

30 mV

100 mV

Spikes peak-peak, typ. (bandwidth: 20 MHz)

60 mV

20 mV

60 mV

Adjustment range

24 … 28 V

24 … 28 V

24 … 28 V

Product function Output voltage adjustable

Yes

Yes

Yes

Output voltage setting

via potentiometer; max. 120 W (144 W up to 45°C)

via potentiometer; max. 240 W (288 W up to 45°C)

via potentiometer; max. 480 W (576 W up to 45°C)

Status display

Green LED for 24 V OK

Green LED for 24 V OK

Green LED for 24 V OK

Signaling

Electronic contact (NO contact, contact rating 60 V DC/0.1 A) for 24 V O.K. or diagnostic interface

Electronic contact (NO contact, contact rating 60 V DC/0.1 A) for 24 V O.K. or diagnostic interface

Electronic contact (NO contact, contact rating 60 V DC/0.1 A) for 24 V O.K. or diagnostic interface

On/off behavior

Overshoot of Vout < 2 %

Overshoot of Vout < 2 %

Overshoot of Vout approx. 3 %

Startup delay, max.

0.5 s

0.5 s

0.5 s

Voltage rise, typ.

100 ms

200 ms

100 ms

Rated current value Iout rated

5 A

10 A

20 A

Current range

0 … 5 A

0 … 10 A

0 … 20 A

  • ● Note

6 A up to +45°C; +60 … +70 °C: Derating 2%/K

12 A up to +45°C; +60 … +70 °C: Derating 2%/K

24 A up to +45°C; +60 … +70 °C: Derating 1%/K

Supplied active power typical

120 W

240 W

480 W

Short-term overload current

  • ● on short-circuiting during the start-up typical

6 A

12 A

30 A

  • ● at short-circuit during operation typical

6 A

12 A

30 A

Product feature parallel switching of outputs

can be set with DIP switch

can be set with DIP switch

Parallel switching for enhanced performance

Yes; switchable characteristic

Yes; switchable characteristic

Numbers of parallel switchable units for enhanced performance

2

2

Efficiency

Efficiency at Vout rated, Iout rated, approx.

90.2 %

92.8 %

95.1 %

Power loss at Vout rated, Iout rated, approx.

13 W

18 W

25 W

Power loss [W] during no-load operation maximum

2 W

2.2 W

2.6 W

Closed-loop control

Dynamic load smoothing (Iout: 10/90/10 %), Uout ± typ.

2 %

2 %

3 %

Load step setting time 10 to 90%, typ.

1 ms

2 ms

0.5 ms

Load step setting time 90 to 10%, typ.

1 ms

2 ms

0.5 ms

Setting time maximum

2 ms

3 ms

1 ms

Protection and monitoring

Output overvoltage protection

< 32 V

< 32 V

< 32 V

Current limitation, typ.

6 A

12 A

30 A

Property of the output Short-circuit proof

Yes

Yes

Yes

Short-circuit protection

Shutdown and periodic restart attempts

Shutdown and periodic restart attempts

Shutdown and periodic restart attempts

Overcurrent overload capability in normal operation

overload capability 150 % Iout rated up to 5 s/min

overload capability 150 % Iout rated up to 5 s/min

overload capability 150 % Iout rated up to 5 s/min

Safety

Primary/secondary isolation

Yes

Yes

Yes

Galvanic isolation

Safety extra low output voltage Vout according to EN 60950-1

Safety extra low output voltage Vout according to EN 60950-1

Safety extra low output voltage Vout according to EN 60950-1

Protection class

Class I

Class I

Class I

Leakage current

  • ● maximum

3.5 mA

3.5 mA

3.5 mA

CE mark

Yes

Yes

Yes

UL/cUL (CSA) approval

cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)

cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)

cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)

Explosion protection

FM approval

CB approval

Yes

Yes

Yes

Regulatory Compliance Mark (RCM)

No

No

No

Marine approval

in process: DNV GL, ABS

in process: DNV GL, ABS

in process: DNV GL, ABS

Degree of protection (EN 60529)

IP20

IP20

IP20

EMC

Emitted interference

EN 55022 Class B

EN 55022 Class B

EN 55022 Class B

Supply harmonics limitation

EN 61000-3-2

EN 61000-3-2

EN 61000-3-2

Noise immunity

EN 61000-6-2

EN 61000-6-2

EN 61000-6-2

Operating data

Ambient temperature

  • ● during operation

-25 … +70 °C

-25 … +70 °C

-25 … +70 °C

  • — Note

with natural convection

operating range with natural convection -40 °C … 70 °C, in the range of -25 °C … 0 °C monotonous ramp up of the output voltage

operating range with natural convection -40 °C … 70 °C, in the range of -25 °C … 0 °C monotonous ramp up of the output voltage

  • ● during transport

-40 … +85 °C

-40 … +85 °C

-40 … +85 °C

  • ● during storage

-40 … +85 °C

-40 … +85 °C

-40 … +85 °C

Humidity class according to EN 60721

Climate class 3K3, 5 … 95% no condensation

Climate class 3K3, 5 … 95% no condensation

Climate class 3K3, 5 … 95% no condensation

Mechanics

Connection technology

Push-in terminals

Push-in terminals

Push-in terminals

Connections

  • ● Supply input

L1/+, L2/N/-; PE PushIn for 0.5 … 4 mm² single-core/finely stranded

L1/+, L2/N/-; PE PushIn for 0.5 … 4 mm² single-core/finely stranded

L1/+, L2/N/-; PE PushIn for 0.5 … 4 mm² single-core/finely stranded

  • ● Output

+1, +2, -1, -2, -3: PushIn for 0.5 … 2.5 mm²

+1, +2, -1, -2, -3: PushIn for 0.5 … 2.5 mm²

+1, +2, -1, -2, -3: PushIn for 0.5 … 6 mm²

  • ● Auxiliary

13, 14 (alarm signal): 1 push-in terminal each for 0.2 … 1.5 mm²

13, 14 (alarm signal): 1 push-in terminal each for 0.2 … 1.5 mm²

13, 14 (alarm signal): 1 push-in terminal each for 0.2 … 1.5 mm²

Width of the enclosure

35 mm

45 mm

70 mm

Height of the enclosure

135 mm

135 mm

135 mm

Depth of the enclosure

125 mm

125 mm

155 mm

Required spacing

  • ● top

45 mm

45 mm

45 mm

  • ● bottom

45 mm

45 mm

45 mm

  • ● left

0 mm

0 mm

0 mm

  • ● right

0 mm

0 mm

0 mm

Product feature of the enclosure housing for side-by-side mounting

Yes

Yes

Yes

Installation

Snaps onto DIN rail EN 60715 35×7.5/15

Snaps onto DIN rail EN 60715 35×7.5/15

Snaps onto DIN rail EN 60715 35×7.5/15

Electrical accessories

Buffer module, redundancy module

Buffer module, redundancy module

Buffer module, redundancy module

Mechanical accessories

Identification labels SIMATIC ET 200SP 6ES7193-6LF30-0AW0

Identification labels SIMATIC ET 200SP 6ES7193-6LF30-0AW0

Identification labels SIMATIC ET 200SP 6ES7193-6LF30-0AW0

Other information

Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

Accessories

SITOP RED1200 redundancy module

6EP4346-7RB00-0AX0

Input/output: 12 V DC, 24 V, 48 V/20 A (maximum total current)
Suitable for decoupling two SITOP power supplies with a maximum of 10 A output current each

SITOP RED1200 redundancy module

6EP4347-7RB00-0AX0

Input/output: 12 V DC, 24 V, 48 V/40 A (maximum total current)
Suitable for decoupling two SITOP power supplies with a maximum of 20 A output current each

SITOP SEL1200

6EP4438-7FB00-3DX0

Selectivity module, 8-channel, switching
Input: 24 V DC
Output: 24 V DC/10 A per output
Adjustable response threshold 2 … 10 A

SITOP SEL1400

6EP4438-7EB00-3DX0

Selectivity module, 8-channel, limiting
Input: 24 V DC
Output: 24 V DC/10 A per output
Adjustable response threshold 2 … 10 A

SIMATIC ET 200SP equipment labels

6ES7193-6LF30-0AW0

160 equipment labeling plates, 10 sheets (160 labels)

PLC's
PLC's
I/O systems for in cabinets
I/O systems for in cabinets
I/O systems for in the field
I/O systems for in the field
Software
Software
HMI
HMI
Industrial PC's
Industrial PC's
Industrial IoT Gateway
Industrial IoT Gateway
Automatic door controls
Automatic door controls

Did you know, we are an entrusted Siemens approved partner?

Loading...